Looking for Exclusive Agency and Distributor! Welcome Contact:0086-18966276297 0086-577-61718910

page_head_bg

Factory Supply Combiner Box With Spd - B+C three phase Metal oxide varistor Surge arrestor, surge protection 60KA HS2-60 – HONI electric


Product Detail

Product Tags

Related Video

Feedback (2)

The corporate keeps towards the operation concept "scientific administration, superior quality and performance primacy, client supreme for Pedal Dual Spspd 1000v, Pv Spd, Ac Spd 1p 40ka, All prices depend upon the quantity of your order; the more you order, the more economical the price is. We also offer good OEM service to many famous brands.
Factory Supply Combiner Box With Spd - B+C three phase Metal oxide varistor Surge arrestor, surge protection 60KA HS2-60 – HONI electric Detail:

Features/Benefifits

Easy installation or retrofifit
Din-rail mountable
Fail-safe /self-protected design
Remote indicator (optional) with 3 pin NO/NC contact
IP20 fifinger-safe design
Visual indicator
Small foot print

Plug-in format

HS25-B60 is the range of devices for discharging induced transient overvoltages (Type 1+2 / Class I+II), in accordance with EN/IEC 61643-11. DIN rail plug-in format.
Ability to discharge lightning currents (10/350μs) and induced voltage surges (8/20 μs).
■Suitable for the second stage of protection in supply distribution panels.
■Discharge capacity with an 8/20 μs waveform. Imax: 60 kA.
■Exclusive devices for TNS, TNC, TT , IT earthing systems.
■Exclusive devices which are compatible with Power Line Communication networks.
■Biconnect – two types of terminal: for rigid or flflexible cable and for fork type comb busbar.
■Available with optional remote signalling.

Data sheet

TypeTechnical DataMaximum continuous voltage (UC) (L-N)

HS25-B60

 

275 / 320 / 385 / 420V

Maximum continuous voltage (UC) (N-PE)

275V

SPD to EN 61643-11, SPD to IEC 61643-11

Type 1+2 , class I+II

Lightning impulse current (10/350μs) (Iimp)

12.5kA

Nominal discharge current (8/20μs) (In)

30kA

Maximum discharge current (8/20μs) (Imax)

60kA

Voltage protection level (Up) (L-N)

≤ 1.5 / 1.8 / 2.0 / 2.2kV

Voltage protection level (Up) (N-PE)

≤ 1.5kV

Response time (tA) (L-N)

< 25ns

Response time (tA) (N-PE)

< 100ns

Thermal Protection

YES

Operating State/Fault Indication

Green (good) / White or Red (replace)

Degree of protection

IP 20

Insulating material / flammability class

PA66,UL94 V-0

Temperature range

-40ºC~+80ºC

Altitude

13123 ft [4000m]

Conductor Cross Section (max)

35mm2 (Solid) / 25mm2 (Flexible)

Remote Contacts (RC)

Optional

Format

Pluggable

For mounting on

DIN rail 35mm

Place of installation

indoor installation

Dimensions

HS2-60 Power Surge Protector 001

1. product design standard: this product is designed according to relevant international standards IEC, and its performance meets the requirements of national standard GB 18802.1-2011 “low voltage surge protector (SPD) part 1: performance requirements and test methods of surge protector for low voltage distribution system”.

2. Scope of product use: GB50343-2012 Technical Code for Lightning Protection of Building Electronic Information System

3 Selection of surge protector: The primary SPD must be set in the main distribution box at the entrance of building power supply.

4. Product features: This product has the characteristics of low residual voltage, fast response speed, large current capacity (impulse current Iimp(10/350μs) is 25kA/ line, long service life, simple maintenance and convenient installation, etc.

5.Working temperature: -25℃ ~+70℃, working humidity: 95%.

Quality assurance:

1. Strict control on choose of the raw material sources.
2. Speciific technology guide for the production of each product.
3. Completed quality testing system for the semi-finished products and finised products.


Product detail pictures:

Factory Supply Combiner Box With Spd - B+C three phase Metal oxide varistor Surge arrestor, surge protection 60KA HS2-60 – HONI electric detail pictures


Related Product Guide:

We keep on with the theory of "quality first, provider initially, constant improvement and innovation to meet the customers" with the management and "zero defect, zero complaints" as the standard objective. To great our company, we deliver the merchandise using the fantastic excellent at the reasonable price for Factory Supply Combiner Box With Spd - B+C three phase Metal oxide varistor Surge arrestor, surge protection 60KA HS2-60 – HONI electric , The product will supply to all over the world, such as: Zurich, Bogota, Iran, During the 10 years of operating, our company always try our best to bring consumption satisfaction for user, built a brand name for ourselves and a solid position in the international market with major partners come from many countries such as Germany, Israel, Ukraine, United Kingdom, Italy, Argentina, France, Brazil, and so on. Last but not least, price of our products are very suitable and have fairly high competition with other companies.
  • This company has a lot of ready-made options to choose and also could custom new program according to our demand, which is very nice to meet our needs.
    5 Stars By Judith from Houston - 2017.09.30 16:36
    Product variety is complete, good quality and inexpensive, the delivery is fast and transport is security, very good, we are happy to cooperate with a reputable company!
    5 Stars By Flora from Bulgaria - 2017.02.14 13:19
    Write your message here and send it to us